HXS Series
- Hong Kong's only exit sign series with automatic testing to IEC 62034:2012
- Complies with FSD PPA/104(A) — Circular Letter No. 5/2021 permits automatic monthly functional and annual full-duration tests
- No manual testing — tests run automatically, faults shown locally
- Slim, low-profile design — compact exit signs for tight, discreet installations
Wall Mount | Box Type
Wall Mount | Plate Type
Recessed Mount
Ceiling Mount | Plate Type
HXL Series
Monthly Automatic Testing
Hong Kong Exit Sign Regulations & Testing Requirements
Hoye exit signs are built to meet FSD Circular Letter No. 5/2021 [PPA/104(A), 5th Revision] — and the international standards behind them:
Lettering and colours — bilingual legends, minimum 125 mm letters or 125 × 125 mm pictograms, green/white contrast as required.
Battery and brightness — 3-hour rated battery (2 hours required), 90% brightness within 5 seconds of mains failure.
Directional exit signs — required where an exit is not immediately visible
Mounting — slim and recessed bodies fit the standard 2 m–2.5 m position directly above doorways.
Testing — the required monthly and annual tests run automatically to IEC 62034:2012; faults are shown on the fitting.
Standards: FSD Circular 5/2021 · IEC 62034:2012 · BS 5266-1:2016 · BS EN 1838:2013 · EN 60598 · EN 61347 · EN 62384 · EN 55015 · EN 61000 · EN 61547
Fire Services Department requirements
The requirements below come from two official circular letters:
- FSD Circular Letter No. 5/2021 — Emergency Lighting [PPA/104(A)] (English | 中文)
- FSD Circular Letter No. 5/2008 — Graphical Symbol Exit Signs (English | 中文)
Source: FSD Circular Letter
Battery and brightness
- At least 2 hours of battery operation
- 90% of required illumination within 5 seconds of power failure
- HXS is rated 3 hours and runs up to 5 hrs
Testing
- Monthly functional test
- Annual full-duration test
- Results recorded in a register
- Automatic testing devices permitted — HXS runs them to IEC 62034
Sign design
- Internally illuminated signs — the approved type
- One uniform design per building
- Letters at least 125 mm, or a 125 × 125 mm graphical symbol
- Green and white, high contrast
- Running-man pictogram, minimum 125 × 125 mm, green on white; directional versions add escape-route arrows
Mounting
- 2 m to 2.5 m above floor level, at the base of the sign
- Directly above the exit doorway
Where this applies
- Licensed and registered premises — restaurants, cinemas, entertainment venues, karaoke, child care centres, converted schools
For contractors
- Registered Class 2 fire service installation contractor
- Completion certified on Form FS 251
Choosing a size
- 180 mm — standard doorways and corridors
- 270 mm — longer escape routes, directional
- 400 mm — maximum visibility, letter legends
- All sizes share the same IEC 62034 automatic testing
Common questions
- Exit sign height — 2 m to 2.5 m above floor level
- Exit sign size — 125 mm letters or a 125 × 125 mm pictogram minimum
- Exit sign colour — green and white, high contrast
- Bilingual lettering — English and Chinese, or an approved graphical symbol instead
- What is IEC 62034 — the international standard for automatic test systems for battery-powered emergency escape lighting; HXS tests itself to this standard
- Battery duration — at least 2 hours by law; HXS is rated 3 hours and runs up to 5
- Testing frequency — monthly functional test and annual duration test, results kept in a register
- Who can install — a registered Class 2 fire service installation contractor, completion certified on Form FS 251
- Existing buildings — mixed exit sign designs are acceptable, but one uniform type is recommended as signs are replaced
- LED lifespan — LED exit signs run for years with no lamp replacement; the battery is the only service item
- Route coverage — signs must mark every exit and every change of direction along the escape route
- Records — keep the test register ready for licensing inspections
Download: Exit Sign Requirements (PDF) Exit-Sign-Requirements-FSD-PPA104A
下載:出路牌規定(PDF) 出路牌規定-出口指示牌-FSD-PPA104A
Emergency lighting test records & log book
After testing an emergency lighting unit, FSD requires the result to be logged. PPA/104(A) C.14(b): the annual full-duration test result must be entered in a register; monthly test results are recorded in the same log book.
The register follows BS 5266-1 (the standard referenced by FSD Circular 5/2021): Annex J defines the log book contents — installation details, equipment register, monthly and annual test results, faults and repairs; Annex M provides the model forms — inspection and test certificate, test record, fault action record.
A ready-to-use template is provided: Emergency Lighting Inspection and Test Certificate & Record Forms (BS 5266-1 Annex M) — download the PDF.
Download: Emergency Lighting Inspection and Test Certificate & Record Forms (BS 5266-1 Annex M)